Motor Load Data
For design purposes motor full load currents for electricity supplies of 11kV, 3.3kV and 400V 50Hz three phase are taken from averaged manufacturers’ data for nominal 1500rpm motors and are shown in table 1.
Table 1 – Motor Ratings (output) Vs Full Load Current
| | Motor Rating | Full Load Current - Amps | | kW | 400V | 3300V | 11000V | | 0.06 | 0.28 | | | | 0.09 | 0.38 | | | | 0.12 | 0.44 | | | | 0.18 | 0.66 | | | | 0.25 | 0.8 | | | | 0.37 | 1.05 | | | | 0.55 | 1.47 | | | | 0.75 | 1.96 | | | | 1.1 | 2.58 | | | | 1.5 | 3.46 | | | | 2.2 | 4.87 | | | | 3 | 6.72 | | | | 3.7 | 8.2 | | | | 4 | 8.57 | | | | 5 | 10.5 | | | | 5.5 | 11.7 | | | | 7.5 | 15.25 | | | | 11 | 21.79 | | | | 15 | 29.5 | | | | 18.5 | 35.75 | | | | 22 | 42.43 | | | | 30 | 57.3 | | | | 37 | 69.8 | | | | 45 | 84 | | | | 55 | 103 | | | | 75 | 137 | | | | 90 | 164 | | | | 110 | 197 | 26 | | | 132 | 240 | 31 | | | 160 | 282 | 39 | | | 200 | 356 | 46 | | | 250 | 441 | 57 | | | 315 | 552 | 70 | | | 355 | 636 | 79 | | | 400 | 710 | 88 | | | 450 | 800 | 95 | | | 500 | 890 | 107 | | | 560 | 1000 | 119 | | | 630 | | 133 | | | 710 | | 146 | | | 800 | | 164 | 50 | | 1000 | | 200 | 60 | | 1120 | | 223 | 67 | | 1250 | | 249 | 75 | | 1400 | | 280 | 84 | | 1600 | | 319 | 96 | | |